Pressure piping, vessel manufacturing, flame arrester type, ATEX certification

Pressure piping, vessel manufacturing, flame arrester type, ATEX certification

banner3

Strictly control the entire manufacturing process to ensure the stable operation of chemical production equipment

Strictly control the entire manufacturing process to ensure the stable operation of chemical production equipment

Deflagration Flame Arrestor

The deflagration-proof flame arrestor is a safety device installed on flammable gas/vapor pipelines or equipment nozzles. It allows normal gas flow while stopping the propagation of backfire from subsonic deflagration flames (

  • Parameters
  • Drawing
  • Application areas

Working Principle

Slit Quenching:When flame enters narrow channels formed by corrugated plates, wire mesh or porous metal (gap smaller than the MESG of the medium), heat is rapidly dissipated, thus extinguishing the flame.

Deflagration Resistance:Blocks subsonic deflagration; not suitable for detonation resistance.

Burn Resistance:Withstands short-duration burning to prevent the flame arrester element from being damaged by sustained combustion.



Structural Composition

Shell:Carbon steel / 304 / 316L stainless steel, flange connection (GB, HG, ANSI, DIN, GOST standards)

Flame Arrestor Element (Core Component):304 or 316L corrugated plates, multi-layer wire mesh or porous metal; gaps designed according to the MESG of the medium.

Sealing Components:PTFE / fluoroelastomer (FKM) / metal graphite gaskets



Qualifications & Certifications

Type Certification for IIA Deflagration Resistance,Type Certification for IIB Deflagration Resistance,ATEX Type Certification



Applicable Standards

GB 5908-2024

ISO 16852、SH/T 3413-2019

EN ISO 16852-2016、EN 1127-1-2019



Parameter

Parameter Standard Version Premium Version Remarks
Nominal Diamete DN25 ~ DN1200 Customizable Matches pipeline nominal diameter
Pressure Class PN10/16/25/40 PN16 ~ PN40 High pressure ≥6.4MPa available by customization
Design Temperature -40℃ ~ 400℃ -60℃ ~ 450℃ 316L / Duplex steel for high-temperature service
Flame Arrest Grade Deflagration-resistant (Group IIA/IIB) Dual grade IIA & IIB Group IIC requires detonation-resistant type
MESG Clearance ⅡA<0.9mm;ⅡB<0.5mm ⅡA≤0.8mm;ⅡB≤0.45mm Safety margin: 0.8–0.9 times
Deflagration Resistance Test Passes 6 consecutive deflagration tests 6 deflagration tests + 1-hour burn resistance GB 5908-2024
Pressure Drop ≤5kPa(DN100,10m/s) ≤3kPa Lower value represents better performance
Burn Resistance Duration End fitting: 1h; In-line: ≤10min End fitting: 1.5h Test medium: Propane 4%±0.4% volume concentration
Explosion-proof Mark/td> Exd ⅡBT4 Exd ⅡBT6 Suitable for chemical hazardous explosion zones